EOCR-3DM : Relay bảo vệ quá dòng, mất pha, mất cân pha, đảo pha, lock rotor của Samwha

EOCR-3DM : Relay bảo vệ quá dòng, mất pha, mất cân pha, đảo pha, lock rotor của Samwha (Bây giờ là Schneider Electric)

Main Features

Protection

Protective Item

Trip Time

Over-current

DEF : 0.2 ~ 30sec INV : 1 ~ 30

Undercurrent

0.5~30sec(DEF)

Phase Loss

within 3sec

Phase Unbalance

0.1sec

Phase Reversal

8sec

Locked Rotor

Lock

0.5sec after dt

stall

1~10sec

A Lert

50~100% of Set Current

Specficication

Model

3DM /FDM

Current Setting Range

Over-Current(oc)

0.1~800A(Over 20A with External CTs)

Under-Current(uc)

0.5~under OC setting

Time Setting

Starting Delay Time(dt)

OFF~200sec

Over-Current Trip (ot)

DEF:0.2~30sec/INV:1~30

Under-Current Trip (ut)

0.5~30sec(DEF)

Conrol Power

220

85~250VAC/DC, 85~50VAC/DC, 50/60Hz

Output Relay

O.L

2-SPST, 3A/250VAC, Resistive

A.L

1-SPST, 3A/250VAC, Resistive

Environment

Temperature

Store

-30 ~80 ℃

Operation

-30 ~60 ℃

Humidity

30~85%RH, Non-condensation

Display

7-Segment LEDs

3 Phase current, 3 Trip causes, Run time

Bar-Graph

% of existing Current vs OC setting current

Mounting

35mm DIN-Rail